Abstract: High Impedance Faults (HIFs) are the most challenging problems faced by utility engineers. These HIFs remain undetected due to the nature of the faults. Detection, Identification of Location and Estimation of the distance of the fault is presented in this work. Review of Literature and Research gaps into HIFs will be presented.

The research work is concerned the development of an Robust HIF detection Scheme that uses zero sequence analytical redundancy method which is invariant to modelling errors. Identification of the faulted bus and estimation of the distance of the HIF using single and double ended measurements are some of the important proposed aspects.

Detection of HIF using an unknown input observer (UIO) will be presented. Robust detection scheme using three methods are described. A two terminal model was considered to two ended measurement using PMUs for synchronized measurements at both terminals. A fourth order state space eigen value model was proposed to fault location identification. An IEEE 39 bus system was considered for this study. Preliminary results illustrate the accuracy of the location with variation fault resistance and in the presence of noise.

Title: High Impedance Faults in Distribution Networks: Detection, Location Identification and Distance Estimation
Date: November 30, 2026 at 03:00 PM
Venue: ESB 244
Speaker: Mr. Arjundas K (EE23D027)
Guide: Dr. Swarup K S
Type: PHD seminar